CIRCUIT BREAKER
| NSN | 5925-00-089-5596 |
|---|---|
| NIIN | 000895596 |
| Class (FSC) | 5925 · CIRCUIT BREAKERS |
| Group (FSG) | 59 · Electrical And Electronic Equipment Components |
| Unit of issue | EA |
| DMIL | A |
Item definition
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES:CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
Technical characteristics
| OVERALL LENGTH | INCHES NOMINAL 3.330 |
|---|---|
| OVERALL HEIGHT | INCHES NOMINAL 1.530 |
| OVERALL WIDTH | INCHES NOMINAL 2.530 |
| POLE QUANTITY | 2 |
| MOUNTING FACILITY TYPE AND QUANTITY | THREADED HOLE(S) 4 |
| THREAD QUANTITY PER INCH | 32 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 50.0 |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 250.0 |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 1000.0 |
| CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| TRIP RELEASE METHOD | ALL LOCATIONS MAGNETIC-HYDRAULIC |
| TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS TIME DELAY |
| RESET METHOD | MANUAL |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| ACTUATOR FUNCTION | TRIP-RESET |
| NOMINAL THREAD SIZE | INCHES 0.138 |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MINIMUM AT 150 PCT 7.000 AND MAXIMUM AT 150 PCT 31.000 AND MINIMUM AT 300 PCT 1.500 AND MAXIMUM AT 300 PCT 4.000 AND MINIMUM AT 325 PCT 0.600 AND MAXIMUM AT 325 PCT 2.000 |
| FREQUENCY IN HERTZ | 60.0 |
| MATERIAL | CASE PLASTIC |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TERMINAL TYPE AND QUANTITY | THREADED STUD 4 |
Source: US Defense Logistics Agency (DLA) FLIS open data. For information only; price and stock are not stated, availability is confirmed at quotation.